vegabondsheyla 2025. 6. 15. 15:02

DEP 80001010 

The separation distances have in general been arrived at through consequence modelling of relevant failure scenarios (e.g., tank top fire, or loss of containment via a 25 mm (1 inch) hole in a pressurized system), giving distances to blast
overpressures and radiation levels.

 

GS EP SAF 253 Fire zone

20 mm (1) leak diameter 

- Corresponds to ¾ inch fitting rupture scenario (rounded to the nearest upper natural number)

 

SP-1258 QRA & PEM

Generally 22mm hole size covers about 90% of the leak frequency of an isolatable segment/equipment. It had been a practice in PDO to apply 22mm as credible hole size for different PEM calculations.