Gas Detector Alarm Set Point (Examples) 본문
| [1] | Setting | Unit | Remark | |
| IR Point detector | ||||
| flammable gas (HC) point detectors | Alert threshold | 20% | LEL | |
| Alarm threshold | 50% | LEL | ||
| flammable gas (HC) point detectors in machinery enclosures or building containing a continuous or primary grade of release |
Alert threshold | 15% | LEL | |
| Alarm threshold | 25% | LEL | ||
| flammable gas (H2) point detectors | Alarm threshold | 5% | LEL | |
| Control action threshold | 10% | LEL | ||
| Open path detector (최대 remote distance가 있음) | Low level alarm | 0.5 | %LEL*m | It gives an alarm if there is a flammable gas cloud of 5% LEL over a distance of 10m. |
| High level alarm | 1 | %LEL*m |
| [2] | |||
| Type | Alarm Level 1 | Alarm Level 2 | Note |
| Flammable gas point sensor inside turbine / compressor hood / compartment | 10% LFL | 40% LFL | |
| Flammable gas point sensor process plant and HVAC inlets | 10% LFL | 40% LFL | |
| Flammable gas line of sight sensor | 1 LFL-m | 2 LFL-m | See Note (1) |
| Hydrogen sulphide (H2S) point sensor | 10 ppm (vol) | 40 ppm (vol) | |
| Hydrogen sulphide (H2S) line of sight sensor | To be determined | 100 ppm-m | See Note (2) |
| Hydrogen fluoride (HF) point sensor | 5 ppm | 10 ppm | See Note (3) |
| Carbon Dioxide (CO2) | 5,000 ppm (vol) | 30,000 ppm (vol) | |
| Carbon Monoxide (CO) | 25 ppm (vol) | 200 ppm (vol) | |
| Chlorine (Cl2) | 1 ppm (vol) | 3 ppm (vol) | |
| Oxygen Deficiency | 19.5 % (vol) | ||
| Oxygen Enrichment | 23 % (vol) | ||
| Sulphur dioxide (SO2) | 2 ppm (vol) | 5 ppm (vol) | |
| Heat Detectors (fusible plugs, frangible bulbs, polyflow) | 68 °C (155 °F) | See Note (4) | |
| Notes | |||
| 1. For comfined areas with "heavy HC" greater than C3, use 0.5LFL*m for alarm level 1. | |||
| 2. H2S LOS are emerging into the market. Guidance for their use is currently under review. | |||
| 3. These are typical values. Actual HF alarm levels are subject to local conditions and requirement. | |||
| 4. In areas of high ambient temperature, heat detectors to be set at 30C(50F) above the anticipated ambient temperature or nearest standard fixed setting above 30C(50F). | |||